Sizes of cables and wires

What is a cable cross-section? And what does cable diameter mean?
The cable cross-section is a surface measurement (in mm²) and the cable diameter is a length measurement (in mm).
The cross-section of a cable is defined by the front surface of the cut wire material. Only the conductive components are taken into account, insulation material is not included. For multi-stranded or fine-stranded cables (wires), the front surfaces of the individual fine strands are added together. There is some “space” in between, for example, a fine-stranded cable has a larger outer diameter than a solid cable with the same cross-section. In Europe, the cross-section is usually given in mm².
The cross-section of a cable required for the respective application depends largely on the current which is required: the more current is to flow through the cable, the larger the cable cross-section. The cable length must also be taken into account, and the type of installation and the ambient temperature also play a role, as these components directly influence the current that a cable can transmit. A cable with a large cross-section can carry more current and has a lower resistance.
The cable diameter (ø) in mm determines the size or the outside diameter of a cable. The maximum diameter is determined, measured on the outer insulation.
Der Unterschied zwischen Kabel, Leitungen, Adern und Litzen (Kopie 1)
Die Begrifflichkeiten Kabel und Leitungen werden oft sinngemäß gleichgestellt. Dies ist jedoch fachlich nicht ganz korrekt. Wir gehen genauer auf die Unterschiede zwischen den beiden Begriffen ein:
Die Bezeichnung Kabel meint grundsätzlich eine ummantelte elektrische Leitung. Ein Kabel hat einen mechanischen Schutz und ist zudem gegen Umwelteinflüsse geschützt. Denn Kabel sind für die feste Verlegung (z. B. im Erdreich oder auf dem Meeresgrund) vorgesehen und in der Regel für uns nicht sichtbar.
Leitungen hingegen sind der Überbegriff für einzelne oder mehrere innenliegende Leiter, die mit einer Isolation umhüllt sind. Leitungen begegnen uns in vielen Bereichen des Lebens, da diese oberhalb der Erdoberfläche verbaut werden und im Alltag und in der Industrie zum Einsatz kommen.
Die innenliegenden Leiter werden als Adern bezeichnet. Eine Leitung kann demnach aus einer oder mehreren Adern in einer Umhüllung (Mantel) bestehen.
Eine Ader wiederum besteht entweder aus einem massiven, starren Kupferdraht oder auch aus mehreren dünnen Einzeldrähten, die man Litzen nennt.



When is which unit specified?
We are often asked: When are the dimensions cross-section in mm2 and diameter in mm used for cables and wires? Is there a clear distinction here? Country-specific customs prevail here: In Europe, for example, the cable cross-section is usually given in mm2. However, in Europe, too, in electronics, for cables that are usually small, the cable diameter is usually given in mm. In principle, it can be assumed that for cables with a cross-section of less than 0.5 mm2, only the diameter is often given.
AWG: The American cross-sectional calculation
In the American economic area, however, cable sizes are usually given in AWG numbers, which differ from the nominal sizes common in Europe. The nominal size AWG stands for American Wire Gauge. The AWG system is based on the manufacturing process for wires. In Germany, Europe and many other parts of the world, the cross-sections of cables are given in metric mm². Since AWG is calculated differently, a small AWG value defines a large cross-section. The larger the AWG number, the finer the wire.
Inevitably, there are large differences in the AWG specifications between solid and flexible stranded conductors. And AWG cross-sections do not match the metric cross-sections common in Europe, which is why the AWG values we specify can only be described as approximate. In the converted real metric value, they are usually slightly lower than the mm² we specify.
AWG Metric Comparison Table
WG sizes refer to solid wires. The diameter of twisted wires can exceed the diameter of solid wires by up to 20%.
| AWG-No. | Cross section in mm² | Diameter (ø) in mm | AWG-No. | Cross section in mm² | Diameter (ø) in mm | |
| 4/0 | 102,22 | 11,68 | 19 | 0,65 | 0,91 | |
| 3/0 | 85,01 | 10,40 | 20 | 0,52 | 0,81 | |
| 2/0 | 67,43 | 9,27 | 21 | 0,41 | 0,72 | |
| 1/0 | 53,48 | 8,25 | 22 | 0,33 | 0,64 | |
| 1 | 42,41 | 7,35 | 23 | 0,26 | 0,57 | |
| 2 | 33,62 | 6,54 | 24 | 0,21 | 0,51 | |
| 3 | 26,67 | 5,83 | 25 | 0,16 | 0,46 | |
| 4 | 21,15 | 5,19 | 26 | 0,13 | 0,40 | |
| 5 | 16,77 | 4,62 | 27 | 0,10 | 0,36 | |
| 6 | 13,23 | 4,12 | 28 | 0,081 | 0,32 | |
| 7 | 10,55 | 3,67 | 29 | 0,064 | 0,29 | |
| 8 | 8,37 | 3,26 | 30 | 0,051 | 0,25 | |
| 9 | 6,63 | 2,91 | 31 | 0,040 | 0,23 | |
| 10 | 5,26 | 2,59 | 32 | 0,032 | 0,20 | |
| 11 | 4,17 | 2,30 | 33 | 0,025 | 0,18 | |
| 12 | 3,31 | 2,05 | 34 | 0,020 | 0,16 | |
| 13 | 2,63 | 1,83 | 35 | 0,016 | 0,14 | |
| 14 | 2,08 | 1,63 | 36 | 0,013 | 0,13 | |
| 15 | 1,65 | 1,45 | 37 | 0,010 | 0,11 | |
| 16 | 1,31 | 1,29 | 38 | 0,008 | 0,10 | |
| 17 | 1,04 | 1,15 | 39 | 0,006 | 0,09 | |
| 18 | 0,82 | 1,02 | 40 | 0,005 | 0,08 |
AWG Metic Comparison Table: Conversion of AWG into the units of cable cross-section and cable diameter
You might also be interested in: "Conductor classes for cables and wires"
To the author Johannes Wienecke